# 30 CFR 77.906 — Trailing cables supplying power to low-voltage mobile equipment; ground wires and ground check wires.

- **Chapter:** CHAPTER I—MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR
- **Subchapter:** SUBCHAPTER O—COAL MINE SAFETY AND HEALTH
- **Part:** PART 77—MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES
- **Subpart:** Subpart J—Low- and Medium-Voltage Alternating Current Circuits
- **Snapshot current through:** 2026-08-19
- **Official eCFR:** https://www.ecfr.gov/current/title-30/chapter-I/subchapter-O/part-77/subpart-J/section-77.906

## Current public text

On and after September 30, 1971, all trailing cables supplying power to portable or mobile equipment from low-voltage three-phase resistance grounded power systems shall contain one or more ground conductors having a cross-sectional area of not less than one-half the power conductor. Such trailing cables shall include an insulated conductor for the ground continuity check circuit except where a no less effective device has been approved by the Secretary to assure continuity. Splices made in low-voltage trailing cables shall provide continuity of all components.