{"data":{"chapter":"I","chapterHeading":"CHAPTER I—MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR","citation":"30 CFR 75.601-1","heading":"Short circuit protection; ratings and settings of circuit breakers.","id":"75.601-1","officialUrl":"https://www.ecfr.gov/current/title-30/chapter-I/subchapter-O/part-75/subpart-G/section-75.601-1","part":"75","partHeading":"PART 75—MANDATORY SAFETY STANDARDS—UNDERGROUND COAL MINES","subchapter":"O","subchapterHeading":"SUBCHAPTER O—COAL MINE SAFETY AND HEALTH","subpart":"G","subpartHeading":"Subpart G—Trailing Cables","text":"Circuit breakers providing short circuit protection for trailing cables shall be set so as not to exceed the maximum allowable instantaneous settings specified in this section; however, higher settings may be permitted by an authorized representative of the Secretary when he has determined that special applications are justified:\n\nConductor size AWG or MGM Maximum allowable circuit breaker instantaneous setting (amperes) 14 50 12 75 10 150 8 200 6 300 4 500 3 600 2 800 1 1,000 1/0 1,250 2/0 1,500 3/0 2,000 4/0 2,500 250 2,500 300 2,500 350 2,500 400 2,500 450 2,500 500 2,500"},"meta":{"representation":"json","fullCorpus":"/data/title30-sections.json","snapshot":{"chapterCount":6,"featuredSectionCount":100,"latestAmendedOn":"2026-08-14","latestIssueDate":"2026-08-14","partCount":206,"sectionCount":5954,"upToDateAsOf":"2026-08-19"}}}